Does the Reliance Controls A306A transfer switch transfer the neutral?
M C
from California
October 20, 2020
Answer
The switch does not transfer the neutral. If there is a fault with your generator, it terminates at the generator not the panel. If you had a floating neutral, the fault would terminate at the panel/switch. Most manual transfer switches do not mention this because it is determined by the generator, not the switch.